LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present.

Terminal Identification:

Terminal Legend Function/Description
AC/AC

Low voltage AC input.

- DC +

12VDC @ 1.2 amp continuous supply current.
24VDC @ 750mA continuous supply current.

+ BAT -

Stand-by battery connections. Maximum charge rate 300mA.

AC AC

+DC - BAT +

AC

DC

FACTORY SET AT 12V

CUT J1 FOR 24V

CUT J2 FOR 6V

J1

J2

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.