Altronix FireSwitch108 Data Sheet User Manual

Fireswitch108 managed nac power extender

background image

Input:

• Power input: 120VAC 60Hz, 4.8 amp.

• Two (2) Class A or two (2) Class B FACP inputs.

• Two (2) configurable inputs trigger via Class A or

Class B FACP signal circuits (polarity reversal) or

dry contacts.

Output:

• 24VDC voltage regulated power-limited NAC outputs.

• Output power:

10 amp max. total alarm current.

7 amp max. stand-by without battery back-up.

1 amp with battery back-up including

dedicated Aux. output.

For Canadian applications Stand-by with

battery backup is limited to 0.45 amp.

• 2.5 amp max current per output.

• One (1) auxiliary output rated at 1 amp

(regulated, battery backed up).

0.45 amp for Canadian applications.

• Any NAC can be configured as an Aux. output with or

without battery back-up (special application only).

When set as Aux. output, the output is not supervised.

• Programmable supervised indicating circuit outputs:

Eight (8) Class B or Four (4) Class A,

or any combination of Class A and Class B circuits.

• Thermal and short circuit protection with auto reset.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.

• Automatic switchover to stand-by battery when

AC fails.

• Zero voltage drop when switching over to

battery backup.

Supervision:

• AC fail supervision (form “C” contacts).

• Battery fail & presence supervision (form “C” contacts).

• Low power shutdown. Shuts down DC output terminals

if battery voltage drops below 70-75% for 24V units.

Prevents deep battery discharge.

Special Features:

• Programmable LCD display interface.

• Ethernet port interface for remote programmability

and monitoring.

• 2-wire horn/strobe Sync mode allows audible

notification appliances (horns) to be silenced

while visual notification appliances (strobes)

continue to operate.

• Temporal Code 3, Steady Mode, Input to Output

Follower Mode (maintains synchronization of

notification appliances circuit).

• Compatible with 12VDC or 24VDC fire panels.

• Output loop supervision directed to input 1 or input 2.

• Common trouble Dry N.C. output for reporting

trouble to remote FACP.

• Ground fault detection - Ground fault maximum test

impedance 1,000 ohm.

• Ground fault Dry N.O. output to report ground fault

to remote FACP.

Electrical:

• Operating temperature: 0º C to 49º C ambient.

• BTU/Hr.: 122.84 BTU/Hr.

• System AC input VA requirement: 576VA.

Visual Indicators:

• LCD display - Indicates troubles and conditions of

operation. Trouble Condition Memory facilitates

quick identification of an intermittent/fault

(short circuit, open or ground) which has previously

occurred on one or more signaling circuit outputs.

LCD displays which output the fault has occurred on.

Mechanical:

• Enclosure Dimensions (H x W x D approx.):

15.5” (393.7mm) x 12” (304.8mm) x 4.5” (114.3mm)

- Accommodates up to two (2)12VDC/12AH batteries.

• Product weight (approx.): 12.4 lbs. (5.62 kg).

• Shipping weight (approx.): 13.7 lbs. (6.21 kg).

Specifications

The Altronix FireSwitch108 is a cost effective managed NAC Power Extender. It interfaces

with 12 or 24VDC Fire Alarm Control Panels (FACP) to provide Notification Appliance

Circuit expansion support, for additional horns/strobes to allow ADA compliancy. It also pro-

vides auxiliary power to support system accessories. It delivers electronically regulated and

filtered 24VDC power to Class B or Class A NAC loop circuits. Additionally, a separate 1 amp

auxiliary output for 4-wire smoke detectors is available. Alarm current can be divided between

the eight (8) outputs for powering NAC devices. Outputs are rated at 2.5 amp max., and can

be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All

outputs may be programmed for Input to Output Follower Mode

(output will follow input. i.e. March Time Input, March Time

Output). In non-alarm condition independent loop supervision

for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified

via the steered input (input 1 or input 2). In addition, there are common trouble output terminals [NC, C, NO] which

are used to indicate general loop/system trouble. Two (2) FACP signaling outputs can be employed and directed to

control supervision and power delivery to any combination of the eight (8) outputs. It provides a programmable LCD

display interface, plus an ethernet port interface for remote programmability and monitoring.

FireSwitch108

Managed NAC Power Extender

Rev. DSFireSwitch108_02082013

FireSwitch108

Overview