beautypg.com

Altronix ReServ3WP Installation Instructions User Manual

Page 3

background image

ReServWP

- 3 -

Installation Instructions:

This installation should be made by qualified service personnel and should conform to all local codes and in accordance

with the National Electrical Code. This product contains no serviceable parts.

1. Remove back plate inside enclosure by removing the four (4) mounting screws.

2. Mark and drill desired knockouts on the enclosure to facilitate wiring (Fig. 1, pg. 3).

Note: It is required to use UL Listed outdoor rated conduit hubs with a minimum outdoor rating of 4X.

3. Secure back plate inside enclosure with the four (4) mounting screws.

4. Mount unit in desired location with the appropriate fasteners utilizing the holes provided on the

mounting brackets (Figs. 5-6, pg. 8). Secure enclosure to earth ground.

Note: This product needs to be secured to the building/pole before operation.

5. Connect AC power mains to terminals marked [L & N], connect ground to terminal marked [G] (Figs. 2-4, pg. 5-7).

Use 18 AWG or larger for all power connections (Battery, output) (Figs. 2-4, pg. 5-7).

Use 18 AWG to 22 AWG for power limited circuits (AC Fail/Low Battery reporting) (Figs. 2-4, pg. 5-7).

Note: A readily accessible disconnect device shall be incorporated in the building installation wiring.

6. The LEDs on the power supply board will illuminate when AC power is present.

7. Measure output voltage before connecting cameras/devices to outputs. This helps avoid potential damage.
8. ReServ3WP only - Adjust voltage for every two (2) outputs using the corresponding trimpot(s) on the board prior

to connecting devices.

9. Connecting cameras/devices:

ReServ1WP - Connect 12VDC cameras/devices to terminals marked [P 1-4, N 1-4] (Fig. 2, pg. 5).

Connect 24VAC cameras/devices to terminals marked [5-16] (Fig. 2, pg. 5).

ReServ2WP - Connect 24VAC cameras/devices to terminals marked [1-16] (Fig. 3, pg. 6).

ReServ3WP - Connect 12VDC cameras/devices to terminals marked [P 1-16, N 1-16] (Fig. 4, pg. 7).

10. Connect batteries to terminals marked [-- BAT + ] (Figs. 1-3, pg. 5-7). Use two (2) 12VDC batteries connected in

series for 24VDC operation (battery leads included).

Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH), Ultratech UT1270 (12V/7AH).

11. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Figs. 2-4, pg. 5-7)

supervisory relay outputs.

12. The power LEDs on the unit for Outputs 1-16 will illuminate when AC power is present (Figs. 2-4, pg. 5-7).

Note: If any of the power LEDs are not illuminated the cause may be due to the following:

a. AC mains and battery fail.

b. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.

c. Unit damaged/defective.

To reset the PTC:

1. Disconnect corresponding camera/device connected to terminals marked [1-16] (Figs. 2-4, pg. 5-7).

2. Eliminate the trouble condition (short circuit or overload).

3. Allow 1 minute for PTC to cool off (reset).

4. Connect corresponding cameras/devices

to terminals marked [1-16] (Figs. 2-4, pg. 5-7).

5. Power LEDs will illuminate indicating

power has been restored to outputs

(Figs. 2-4, pg. 5-7).

WARNING: This installation should be made

by qualified service personnel and should

conform to all local codes and in accordance

with the National Electrical Code.

LED Diagnostics:

Power Supply Board

Red (DC) Green (AC1) Power Supply Status
ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No Dc output.

Right Panel

Left Panel

Suggested Locations

for Wire Entries

Suggested Locations

for Wire Entries

Bottom Panel

Fig. 1