Led diagnostics, Terminal identification – Altronix SMP3 Installation Instructions User Manual

Page 2

background image

LED Diagnostics:

Red (DC)

Green (AC) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present.

Terminal Identification:

Terminal
Legend

Function/Description

AC/AC

Low voltage AC input (see Voltage Output/Transformer Selection Table).
For 6VDC output use 16VAC or higher with 24VA power rating or higher.
For 12VDC output use 16VAC or higher with 40VA power rating or higher.
For 24VDC output use 28VAC with 85VA power rating or higher.
Caution: Do not apply voltage above 28VAC or 45VDC (maximum input rating).

+ DC –

6VDC, 12VDC or 24VDC @ 2.5 amp continuous supply current.

+ BAT –

Stand-by battery connections. Maximum charge rate 350mA.

+ DC --

+ BAT --

AC

AC

AC

DC

SW1
SW2

6 V

12 V

24 V

SW1

CLSD

SW2

OPEN

OPEN

OPEN

CLSD

OPEN

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.