Terminal Identification:

Terminal

Function/Description

Legend

AC / AC

Low voltage AC input (16VAC / 20VA mi.). Altronix part # TP1620.

+ DC -

12VDC @ 1 amp continuous power limited output.

AC FAIL

Used to notify loss of AC power, e.g. connect to audible device or alarm

N.C., C, N.O.

panel. Relay normally energized when AC power is present.
Contact rating 2 amp @ 120VAC / 28VDC

Low Battery

Used to indicate low battery condition, e.g. connect to alarm panel.

N.C., C, N.O.

Relay normally energized when DC power is present.
Contact rating 2 amp @ 120VAC / 28VDC

- BAT +

Stand-by battery connections. Maximum charge rate 200mA.