beautypg.com

Altronix PM224 Installation Instructions User Manual

Page 2

background image

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIPM224 - Rev. 081004

H10D

MEMBER

Terminal Indentification:

Terminal

Function/Description

Legend

AC / AC

Low voltage AC input (24VAC / 40VA min.). Altronix part # TP2440.

+ DC -

24VDC 750 mA continuous power limited output.

AC FAIL

Used to notify loss of AC power, e.g. connect to audible device or alarm

NC, C, NO

panel. Relay normally energized when AC power is present.
Contact rating 2 amps @ 120VAC / 28VDC

Low Battery

Used to indicate low battery condition, e.g. connect to alarm panel.

NC, C, NO

Relay normally energized when DC power is present.
Contact rating 2 amps @ 120VAC / 28VDC

- BAT +

Stand-by battery connections. Maximum charge rate 200mA.