AC Outdoor

Overview:

These Altronix Outdoor Power Supplies provide 24VAC or 28VAC distributed via one or two output(s) for powering
CCTV Cameras, heaters and other video accessories.

WayPoint AC Reference Chart:

Specifications:

Installation Instructions:

Unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.

1. Remove back plane from enclosure prior to mounting (do not discard hardware).
2. Mark and drill desired inlets on the enclosure to facilitate wiring (Fig. 4, pg. 6).

3. Mount unit in desired location. Mark and drill holes to line up with the top and bottom holes of the enclosure flange.

Secure enclosure with appropriate fasteners (Fig. 5 & 5a, pg. 7 and Fig. 6, pg. 8).

4. Mount back plane to enclosure with hardware.

5. Set the input voltage selector switch for 115VAC or 230VAC operation (Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5)

6. To facilitate wire entry utilize weather tight NEMA 4 rated connectors, bushings and cable.

7. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5).

8. Connect unswitched AC power (115VAC/230VAC 50/60 Hz) to terminals marked [L, G, N]

(Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5). Use 14 AWG or larger for all power connections (Output, AC Input).

9. Set illuminated master power disconnect circuit breaker to the (RESET/ON) position (Fig. 1, pg. 3, Fig. 2, pg. 4,

Fig. 3, pg. 5).

10. Measure output voltage on terminals marked [COM, 24V, 28V] before connecting devices (Fig. 1, pg. 3, Fig. 2, pg. 4,

Fig. 3, pg. 5). This helps avoid potential damage.

11. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5).

12. For 24VAC output connect devices to terminals marked [COM, 24V] (Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5).

For 28VAC output connect devices to terminals marked [COM, 28V] (Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5).

13. Set illuminated master power disconnect circuit breaker to the (RESET/ON) position (Fig. 1, pg. 3, Fig. 2, pg. 4,

Fig. 3, pg. 5).

14. LEDs will illuminate indicating each output is powered (Fig. 1, pg. 3, Fig. 2, pg. 4, Fig. 3, pg. 5).

15. Upon completion of wiring, secure enclosure door with latches and optional lock.

Caution: Equipment to be installed / serviced by authorized / trained personnel only.

Shut branch circuit power before installing / servicing equipment.

WayPoint-10A

24VAC

4 amp

5 amp/250V

1.2 amp

0.7 amp

28VAC

3.5 amp

24VAC and 28VAC

3.5 amp

WayPoint-17A

24VAC

7.25 amp

10 amp/250V

1.7 amp

1.0 amp

28VAC

6.25 amp

24VAC and 28VAC

6.25 amp

WayPoint-30A

24VAC

12.5 amp

15 amp/32V

3.5 amp

2.0 amp

28VAC

10 amp

24VAC and 28VAC

10 amp

Altronix

Model Number

Total

Output

Current

(Power)

Fuse

Output

Ratings

115VAC/50/60Hz

Input

Current

Draw

230VAC/50/60Hz

Input

Current

Draw

Output

Voltage

• CE Compliant.
• Surge suppression.
• Individual power output LED indicators.
• Illuminated master power switch w/built-in
circuit breaker.
• Spare fuses included.

• NEMA 4/4X, IP66-11 Rated Outdoor Enclosure.
• Operating Ambient Temperature: -20º C to 50º C.

Enclosure Dimensions (H x W x D):

13.31” (338.074mm) x 11.31” (287.274mm) x