beautypg.com

Altronix PD4UL Installation Instructions User Manual

Pd4ul, Overview, Specifications

background image

Overview:

The PD4UL is a UL Listed Sub-Assembly power distribution module, designed to convert a single DC input into

four (4) individually fuse protected outputs.

Specifications:

INPUT

1P

1N

2P

2N

LED

1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS

F1

3P

3N

4P

4N

F2

F3

F4

N

P

S

DC

Positive (+)

Input

DC

Negative ( --- )

Input

PD4UL

POWER DISTRIBUTING UNIT

Fire Alarm System Power Supply Unit Also suitable for use as a Access Control System Unit Subassembly

.

9B98

Refer to Installation Instructions IIPD4UL - REV

. 030802

Fig. 1

(#P) Positive DC outputs

(#N) Negative DC outputs

Note: DC outputs are power limited only if

power limited power supply is employed.

Caution: To avoid risk of electric shock

or fire hazard replace fuses with the same

type and rating, 3.5 amp/250V.

Do not expose to rain or moisture.

PD4UL - UL Listed Sub-Assembly

Power Distribution Module

Altronix is not responsible for any typographical errors.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIPD4UL - Rev. 051311

E13K

Agency Listings:

• UL Listed Sub-Assembly for Access
Control System Units (UL 294) and
for Power Supplies for Fire Protective
Signaling Systems (UL 1481).

Input:

• 12VDC or 24VDC up to 10 amp.

Outputs:

• Four (4) individually fuse protected outputs @ 2.5 amp
per output max. current (total output current should not
exceed max. current rating of power supply employed).

Fuse Ratings:

• Fuses are rated @ 3.5A/250V.

Visual Indicators:

• Power on green LED indicator.

Board Dimensions (approximate):

5.25”L x 3.25”W x 1”H

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed
by qualified personnel.
1. Refer to Sub Assembly Installation Instruction for mounting Rev. MS042511.
2. Connect the desired power supply output to terminals marked [INPUT] (Fig. 1).

Note: Left terminal is NEG. (-) and right terminal is POS. (+) (Fig. 1).

3. Measure output voltage before connecting devices. This helps avoid potential damage.
4. Connect devices to be powered to terminal pairs 1 to 4, marked [1P - 1N thru 4P - 4N]. All terminals with common
suffix P “1P, 2P...” are same polarity.

Note: This product is a UL Listed Sub-Assembly for use with Altronix UL Listed power supplies

as indicated in the installation manuals for the power supply.

MEMBER

LISTED

SECURITY

SIGNALING