beautypg.com

Altronix PD8UL Installation Instructions User Manual

Overview, Specifications: installation instructions, Agency listings

background image

Overview:

The PD8UL is a UL Listed Sub-Assembly power distribution module, designed to convert a single DC input into
eight (8) individually fuse protected outputs.

Specifications:

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed
by qualified personnel.
1. Refer to Sub Assembly Installation Instructions for mounting Rev. MS042511.
2. Connect the desired power supply output to terminals marked [INPUT] (Fig. 1).

Note: If using DC voltage, left terminal is NEG. (-) and right terminal is POS. (+) (Fig. 1).

3. Measure output voltage before connecting devices. This helps avoid potential damage.
4. Connect devices to be powered to terminal pairs 1 to 4, marked [1P - 1N thru 4P - 4N].
All terminals with common suffix P “1P, 2P...” are same polarity.

Note: This product is a UL Listed Sub-Assembly for use with Altronix UL Listed power supplies

as indicated in the installation manuals for the power supply.

N

COMMON POWER OUTPUTS

P

FUSED POWER OUTPUTS

1

2 3 4

5 6 7

8

D1

INPUT

R1

LED

N

P

S

M ain Fuse

DC Negative (--- )

Input

DC Positive (+)

Input

Fire Alarm System Power Supply Unit

Also suitable for use as a

Access Control System Unit Subassembly.

9B98
Refer to Installation Instructions

IIPD8UL - REV. 030802

Fig. 1

(#P) Positive DC outputs

(#N) Negative DC outputs

Note: DC outputs are power limited

only if power limited power supply

is employed.

Caution: To avoid risk of electric

shock or fire hazard replace fuses

with the same type and rating,

3.5 amp/250V.

PD8UL - UL Listed Sub-Assembly

Power Distribution Module

Altronix is not responsible for any typographical errors.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIPD8UL - Rev. 051311

E13K

MEMBER

Agency Listings:

• UL Listed Sub-Assembly for Access
Control System Units (UL 294) and
for Power Supplies for Fire Protective
Signaling Systems (UL 1481).

Input:

• 12VDC or 24VDC up to 10 amp.

Outputs:

• Eight (8) individually fuse protected outputs @ 2.5 amp
per output max. current (total output current should not
exceed max. current rating of power supply employed).

Fuse Ratings:

• Fuses are rated @ 3.5A/250V.

Visual Indicators:

• Power on green LED indicator.

Board Dimensions (approximate):

5.25”L x 3.25”W x 1”H

LISTED

SECURITY

SIGNALING