Altronix PD8UL Installation Instructions User Manual
Overview, Specifications: installation instructions, Agency listings
Overview:
The PD8UL is a UL Listed Sub-Assembly power distribution module, designed to convert a single DC input into
eight (8) individually fuse protected outputs.
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed
by qualified personnel.
1. Refer to Sub Assembly Installation Instructions for mounting Rev. MS042511.
2. Connect the desired power supply output to terminals marked [INPUT] (Fig. 1).
Note: If using DC voltage, left terminal is NEG. (-) and right terminal is POS. (+) (Fig. 1).
3. Measure output voltage before connecting devices. This helps avoid potential damage.
4. Connect devices to be powered to terminal pairs 1 to 4, marked [1P - 1N thru 4P - 4N].
All terminals with common suffix P “1P, 2P...” are same polarity.
Note: This product is a UL Listed Sub-Assembly for use with Altronix UL Listed power supplies
as indicated in the installation manuals for the power supply.
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1
2 3 4
5 6 7
8
D1
INPUT
R1
LED
N
P
S
M ain Fuse
DC Negative (--- )
Input
DC Positive (+)
Input
Fire Alarm System Power Supply Unit
Also suitable for use as a
Access Control System Unit Subassembly.
9B98
Refer to Installation Instructions
IIPD8UL - REV. 030802
Fig. 1
(#P) Positive DC outputs
(#N) Negative DC outputs
Note: DC outputs are power limited
only if power limited power supply
is employed.
Caution: To avoid risk of electric
shock or fire hazard replace fuses
with the same type and rating,
3.5 amp/250V.
PD8UL - UL Listed Sub-Assembly
Power Distribution Module
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIPD8UL - Rev. 051311
E13K
MEMBER
Agency Listings:
• UL Listed Sub-Assembly for Access
Control System Units (UL 294) and
for Power Supplies for Fire Protective
Signaling Systems (UL 1481).
Input:
• 12VDC or 24VDC up to 10 amp.
Outputs:
• Eight (8) individually fuse protected outputs @ 2.5 amp
per output max. current (total output current should not
exceed max. current rating of power supply employed).
Fuse Ratings:
• Fuses are rated @ 3.5A/250V.
Visual Indicators:
• Power on green LED indicator.
Board Dimensions (approximate):
5.25”L x 3.25”W x 1”H
LISTED
SECURITY