beautypg.com

Altronix VertiLine16CD Installation Instructions User Manual

Page 3

background image

Vertiline16C

- 3 -

9. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the

ON (RESET) position (Fig. 3, pg. 6).

10. The power LEDs (Green) on the faceplate for Outputs 1-16 will illuminate when AC power is present

(Fig. 1a, pg. 4). If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a tripped
PTC caused by a short circuit or overload condition. If all of the LEDs are OFF there may be a complete loss of
supply power to the Vertiline unit or the illuminated master power disconnect circuit breaker is in the OFF position
or the main fuse 1-8 or 9-16 is blown (Fig. 1c, pg. 4).*
To restore the power output for Vertiline16C or Vertiline166C:
1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).
2- Eliminate the trouble condition.
3- Replace the corresponding automotive blade fuse.*
4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
To restore the power output for Vertiline16CD or Vertiline166CD:
1- Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).
2- Eliminate the trouble condition.
3- Allow 1 minute for PTC to cool off.
4- Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).

*Note: Replace fuses with same type and rating:

Output fuses are rated @ 3 amp for all models.
Main fuse ratings:
10 amp for Vertiline16C and Vertiline16CD.
15 amp for Vertiline166C and Vertiline166CD.

Automotive
Blade Fuse