Input:

• Input 115VAC, 60Hz, 4.2 amp.
• Input fuse rated @ 3.5 amp/250V.
• Fire Alarm Panel or Access Control System trigger
inputs. N.O. or N.C. supervised trigger input and
polarity reversal trigger input.

Output:

• 24VDC outputs.
• 10 amp supply current.
• Five (5) PTC protected Class 2 Rated power limited
outputs, rated @ 2 amp.
• Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.

Battery Backup:

• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
• Power fail supervision relay (form “C” contacts).

Visual Indicators:

• AC input and DC output LED indicators
(power supply board).
• Red LEDs indicate condition of power outputs
(multi-output board).
• Power & input trigger LEDs (multi-output board).

Electrical:

• Operating temperature: 0º C to 49º C ambient.
• 122.84 BTU/Hr.
• System AC input VA requirement: 483VA.

Mechanical:

• Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- Accommodates up to two (2) 12VDC/12AH batteries.
• Product weight (approx.): 10.8 lbs. (4.90 kg).
• Shipping weight (approx.): 11.8 lbs. (5.35 kg).

Specifications

Agency Approvals

AL1024ULM

Multi-Output Power Supply/Charger

Rev. DSAL1024ULM - 07112013

AL1024ULM multi-output access control power supply/charger is specifically designed
for use with access control systems and accessories. This unit converts a 115VAC, 60Hz
input into five (5) individually protected Class 2 Rated power limited 24VDC outputs.
Each output will route power to a variety of access control hardware devices including
Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate
in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through
normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal
from an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC
Shutdown, Elevator Recall or it may be used to trigger auxiliary devices.

Overview

AL1024ULM

UL 294

UL Listed for Access Control System Units.

UL 1481 UL Listed Standard for Safety for Fire Protective Signaling Systems.