Altronix AL300ULXJG Data Sheet User Manual
Al300ulxjg power supply/charger

AL300ULXJG is a power supply/charger that converts a 115VAC/60Hz
input into a single 12VDC or 24VDC Class 2 Rated power limited output.
AL300ULXJG
Power Supply/Charger
Rev. DSAL300ULXJG_12052012
Overview
AL300ULXJG
Specifications
Input:
• Input 115VAC, 60Hz, 3.5 amp.
• Input fuse rated @ 3.5 amp/250V.
Output:
• 12VDC or 24VDC selectable output.
Burglar Alarm Applications (UL 603):
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
• 12VDC or 24VDC @ 2.5 amp supply current.
• Class 2 Rated power limited output.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
Visual Indicators:
• AC input, DC output and Battery LED indicators.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr. :
12VDC: 14.71 - 16.63 BTU/Hr.
24VDC: 29.43 - 32.41 BTU/Hr.
• System AC input VA requirement: 345VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
18” (457.2mm) x 14.5” (368.3mm)
x 4.625” (117.48mm)
- Accommodates up to two (2) 12VDC/18AH batteries.
• Product weight (approx.): 8.3 lbs. (3.76 kg).
• Shipping weight (approx.): 9.2 lbs. (4.17 kg).
Agency Approvals
UL 294
UL Listed for Access Control System Units.
UL 603
UL Listed Standard for Power Supplies for Use with Burglar- Alarm Systems.
UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment.