4. Connect devices to be powered:

a. For Power Supply Board connect to terminals marked [– DC + ].
b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked

[1P & 1N thru 4P & 4N] (Fig. 2, pg. 4) or 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3, pg. 4) or 1 to 16 marked
[1P & 1N thru 16P & 16N] (Fig. 4, pg. 4) carefully observing correct polarity.

Note: Measure output voltage before connecting devices. This helps avoid potential damage.
*Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit,
AC mains should be removed.

5. When using stand-by batteries, they must be lead acid or gel type. Connect battery to terminals marked [– BAT +]

(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of AC will result in the loss of output voltage.

6. Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs

marked [NC, C, NO] (Fig. 1a, pg. 3).

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition

ON

OFF

Loss of AC, Stand-by battery supplying power

OFF

ON

No DC output

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal

Function/Description

Legend

L, G, N

Connect 115VAC/230VAC to these terminals:
L to Hot, N to Neutral, G to ground (if used).

– DC +

12VDC / 24VDC @ 4 amp continuous non-power limited output.

AC FAIL

Used to notify loss of AC power, e.g. connect to audible device or alarm

NC, C, NO

panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 120VAC / 28VDC

Low Battery

Used to indicate low battery condition, e.g. connect to alarm panel.

NC, C, NO.

Relay normally energized when DC power is present.
Contact rating 1 amp @ 120VAC / 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate .5 amp.

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module

Terminal Legend

Function/

PD4/PD4CB

PD8/PD8CB

PD16W/PD16WCB

Description

1P to 4P

1P to 8P

1P to16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.

- 2 -