Altronix LPS3AC Installation Instructions User Manual

Page 2

background image

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition or defective unit.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present.

Terminal Identification:

Terminal

Function/Description

Legend

AC/AC

Low voltage AC input (refer to Voltage Output/Transformer Selection Chart).
For 12VDC output use 16VAC with 56VA power rating or higher.
For 24VDC output use 28VAC with 85VA power rating or higher.

--- DC +

12VDC-24VDC @ 2.5 amp continuous output.

--- BAT +

Stand-by battery connections. Maximum charge rate 500mA.

AC FAIL

Used to report loss of AC (e.g. connect to audible device or alarm panel).

N.C., C, N.O.

Relay normally energized when AC power is present.
Contact rating 1 amp @ 120VAC / 28VDC.