LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal

Function/Description

Legend

L, G, N

Connect 115VAC to these terminals:
L to Hot, N to Neutral, G to ground.

– DC +

12VDC / 24VDC @ 6 amp continuous output.

AC FAIL

Indicates loss of AC power, e.g. connect to audible device or alarm

NC, C, NO

panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 115VAC / 28VDC

Low Battery

Indicates low battery condition, e.g. connect to alarm panel.

NC, C, NO

Relay normally energized when DC power is present.
Contact rating 1 amp @ 115VAC / 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate .5 amp.

LG

N

O

F

F

O

N

OPEN - 24VDC
CLOSED - 12VDC

L

O

W

B

A

T

NC

C NO

NC C

NO

A

C

F

A

IL

--- BAT +

--- DC +

AC DC

5A 250V

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIOLS180 - Rev. 010704

E06J

MEMBER