Led diagnostics, Terminal identification – Altronix OLS180 Installation Instructions User Manual
Page 2
LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Function/Description
Legend
L, G, N
Connect 115VAC to these terminals:
L to Hot, N to Neutral, G to ground.
– DC +
12VDC / 24VDC @ 6 amp continuous output.
AC FAIL
Indicates loss of AC power, e.g. connect to audible device or alarm
NC, C, NO
panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 115VAC / 28VDC
Low Battery
Indicates low battery condition, e.g. connect to alarm panel.
NC, C, NO
Relay normally energized when DC power is present.
Contact rating 1 amp @ 115VAC / 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
– BAT +
Stand-by battery connections. Maximum charge rate .5 amp.
LG
N
O
F
F
O
N
OPEN - 24VDC
CLOSED - 12VDC
L
O
W
B
A
T
NC
C NO
NC C
NO
A
C
F
A
IL
--- BAT +
--- DC +
AC DC
5A 250V