10 Supplement

WEIGHTRAC 31 • Profibus PA

43837-EN-131119

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Repeatability

1 % of the measuring range end value

Deviation with bulk solids

The values depend on the quality of the linearization

Deviation under EMC influence

≤ 1 %

Characteristics and performance data
Step response time

4)

≤ 5 s (with damping 1 s)

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +60 °C (-40 … +140 °F)

Process conditions
For the process conditions, please also note the specifications on the type label. The lower value

always applies.
Process pressure

Unpressurized

Process temperature (measured on the

detector tube)

-40 … +60 °C (-40 … +140 °F)

Vibration resistance - sensor

5)

mechanical vibrations up to 1 g in the frequency range

5 … 200 Hz

Vibration resistance - mounted in the

measuring frame

mechanical vibrations up to 1 g in the frequency range

5 … 200 Hz

Electromechanical data - version IP 66/IP 67
Cable entry

Ʋ M20 x 1.5

2 x cable gland M20 x 1.5 (cable: ø 6 … 12 mm), 4 x

blind plug M20 x 1.5
Included: 1 x cable gland M20 x 1.5

Ʋ ½ NPT

5 x closing cap (red) ½ NPT
Included: 3 x cable gland ½ NPT (cable: ø 6 … 12 mm),

4 x blind plug ½ NPT

Spring-loaded terminals for wire cross-section

Ʋ Massive wire, cord

0.2 … 2.5 mm² (AWG 24 … 14)

Ʋ Stranded wire with end sleeve

0.2 … 1.5 mm² (AWG 24 … 16)

Display and adjustment module
Display element

Display with backlight

Measured value indication

4)

Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk

solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).

5)

Tested according to the guidelines of German Lloyd, GL directive 2.