5 set instrument address – VEGA WEIGHTRAC 31 Profibus PA User Manual
Page 32
32
5 Connecting to power supply
WEIGHTRAC 31 • Profibus PA
43837-EN-131119
The digital tachometer is powered by WEIGHTRAC 31. When using
the digital tachometer, you must power WEIGHTRAC 31 with max.
24 V.
The following cable colors are valid if the tachometer is ordered with
cable.
2
1
16
15
A
1
1
24
56
22
11
12
21
22
19
20
18
17
14
13
16
15
12
91
01
1
Fig. 19: Belt speed - plant control system (PLC) or tachometer (analogue)
A Tachometer (digital)
1 Voltage supply - cable colour brown
2 Voltage supply - cable colour white
15 Digital input - cable colour green
16 Digital input - cable colour yellow
5.5 Set instrument address
An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-
dress can be used for function test of the instrument and for con-
nection to a Profibus PA network. Then address must be changed to
integrate additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
The hardware addressing is effective if an address <126 is adjusted
with the address selection switches on the instrument. Hence the
software addressing is no longer effective, the adjusted hardware
address is valid.
Instrument address
Hardware addressing