beautypg.com

VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire Coax probe With SIL qualification User Manual

Page 65

background image

65

10 Diagnostics and service

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44231-EN-130823

Code
Text mes-

sage

Cause

Rectification

F080
General soft-

ware error

– General software error

– Separate operating voltage

briefly

F105
Measured

value is deter-

mined

– The instrument is still in the

start phase, the measured

value could not yet be

determined

– Wait for the end of the

switch-on phase

– Duration depending on

the version and parameter

adjustment max. 5 min.

F113
Communica-

tion error

– EMC interferences

– Transmission error with the

external communication

with 4-wire power supply

unit

– Remove EMC influences

– Exchange 4-wire power

supply unit or electronics

F125
Unpermissi-

ble electronics

temperature

– Temperature of the elec-

tronics in the non-specified

section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

F260
Error in the

calibration

– Error in the calibration car-

ried out in the factory

– Error in the EEPROM

– Exchanging the electronics

– Send instrument for repair

F261
Error in the

instrument

settings

– Error during setup

– Error when carrying out a

reset

– False signal suppression

faulty

– Carry out a reset

– Repeat setup

F264
Installation/

Setup error

– Error during setup

– Check or correct installation

and/or parameter adjust-

ment

– Check probe length

F265
Measurement

function dis-

turbed

– Sensor no longer carries

out a measurement

– Carry out a reset

– Separate operating voltage

briefly

F266
Impermissi-

ble operating

voltage

– Operating voltage below

specified range

– Check electrical connection

– if necessary, increase

operating voltage

F267
No executable

sensor soft-

ware

– Sensor cannot start

– Exchanging the electronics

– Send instrument for repair

The following table shows the error codes and text messages in the

status message "Function check" and provides information on causes

as well as corrective measures.

Function check