7 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44231-EN-130823

This menu item is only available if you have selected interface meas-

urement under the menu item "Application".

You can accept the adjustment of the level measurement also for the

interface measurement. If you select "Yes", the current setting will be

displayed.

If you have selected "No", you can enter the adjustment for the inter-

face separately. Enter the requested percentage value.

For the full vessel, enter the distance value in m matching the per-

centage value.

This menu item is only available if you have selected interface meas-

urement under the menu item "Application". If you have selected "Yes"

in the previous menu item (accept adjustment of the level measure-

ment), the current setting will be displayed.

If you have selected "No", you can enter the adjustment for the inter-

face measurement separately.

Enter the respective distance value in m for the empty vessel cor-

responding to the percentage value.

To damp process-dependent measured value fluctuations, set an

integration time of 0 … 999 s in this menu item.
If you have selected interface measurement under the menu item

"Application", you can adjust the damping for the level and the inter-

face separately.

Setup - Max. adjustment -

Interface

Setup - Min. adjustment -

Interface

Setup - Damping