7 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44231-EN-130823

Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.
The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
To avoid possible errors during parameterization in a non-safe user

environment, a verification procedure is used that makes it possible

to detect parameterization errors reliably. For this, safety-relevant

parameters must be verified before they are stored in the device. In

normal operating condition, the instrument is also locked against

parameter changes through unauthorized access.
For this reason, the instrument is shipped in locked conditon. The PIN

in the delivery status is "0000".

Character string comparison and serial number

You first have to carry out the character string comparison. This is

used to check the character respresentation.
Confirm if the two character strings are identical. The verification texts

are provided in German and with all other menu languages in English.
Afterwards you confirm that the serial number of your instrument was

carried over correctly. This is used to check device communication.

In the next step, the instrument checks the data of the measurement

and decides by means of the evaluation results if a functions test

is required. If a function test is necessary, the following message is

displayed.

Release setup - adjust-

ment