7 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44231-EN-130823

Caution:

During simulation, the simulated value is outputted as 4 … 20 mA cur-

rent value and digital HART signal.
Push the [ESC] key to deactivate the simulation.
Information:

The simulation is terminated automatically 60 minutes after the last

key has been pushed.

With the menu item "Setup" the echo curve it is possible to save at

the time of setup. This is generally recommended; for using the Asset

Management functions it is necessary. If possible, the curve should

be saved with a low level in the vessel.
With this, you can detect signal changes over the operating time. With

the adjustment software PACTware and the PC, the high-resolution

echo curve can be displayed and used to compare the echo curve of

the setup with the actual echo curve.

The function "Echo curve memory" enables storing echo curves of

the measurement.
Under the sub-menu item "Echo curve memory" you can store the

current echo curve.
Parameter settings for recording the echo curve and the settings of

the echo curve itself can be carried out in the adjustment software

PACTware.
With the adjustment software PACTware and the PC the high-reso-

lution echo curve can be displayed and used later on to assess the

quality of the measurement.

With the function "Proof test", the function of the instrument can be

checked on a recurring basis.

During the function test, the safety function must be treated as unsafe.

Keep in mind that the function test influences downstream connected

devices.

Diagnostics - Echo curve

memory

Diagnosis - Proof test