4 Mounting
VEGAFLEX 86 • 4 … 20 mA/HART two-wire
44231-EN-130823
Fig. 7: Mounting of the sensor with inflowing medium
The reference plane for the measuring range of the sensors is the
sealing surface of the thread or flange.
Keep in mind that a min. distance must be maintained below the refer-
ence plane and possibly also at the end of the probe - measurement
in these areas is not possible (dead band). These dead bands are
listed in chapter "Technical data". Keep in mind for the adjustment that
the default setting for the measuring range refers to water.
The process fitting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical
data" or on the type label of the sensor.
Instruments for a temperature range up to 280 °C or up to 450 °C
have a distance piece between process fitting and electronics hous-
ing. Ths distance piece is used for thermal decoupling of the electron-
ics against high process temperatures.
Information:
The distance piece must only be incorporated up to max. 50 mm (2 in)
in the vessel isolation. Only then, a reliable temperature decoupling is
guaranteed.
Measuring range
Pressure
Mounting in the vessel
insulation