6 Set up with the display and adjustment module

VEGAFLEX 83 • Profibus PA

44226-EN-130910

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.
Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.
The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank, when the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
The linearization applies to the measured value indication and the

current output. By activating the appropriate curve, the volume per-

centage of the vessel is displayed correctly. If the volume should not

be displayed in percent but e.g. in l or kg, a scaling can be also set in

the menu item "Display".