beautypg.com

VEGA VEGAFLEX 83 Profibus PA PFA insulated User Manual

Page 3

background image

3

Quick start

VEGAFLEX 83 • Profibus PA

44226-EN-130910

1. In this menu item you can select the application. You can choose

between level and interface measurement.

2. In the menu item "Medium - Dielectric constant" you can define

the type of medium (medium).

3. Carry out the adjustment in the menu items "Min. adjustment" and

"Max. adjustment".

4. A "Linearization" is recommended for all vessels in which the

vessel volume does not increase linearly with the level - e.g. in a

horizontal cylindrical or spherical tank. Activate the appropriate

curve.

5. A "False signal suppression" detects, marks and saves the false

signals so that they are no longer taken into account for level

measurement. We generally recommend a false signal suppres-

sion.

The sensor measures the distance from the sensor (reference plane)

to the product surface.

2

4

5

3

1

2

4

5

3

1

Fig. 3: Measuring ranges - VEGAFLEX 83
1 Reference plane

2 Probe length L

3 Measuring range (default setting refers to the measuring range in water)

4 Upper dead band (in this area no measurement is possible)

5 Lower dead band (in this area no measurement is possible)

Parameterization example