VEGA VEGAFLEX 82 Modbus and Levelmaster protocol User Manual
Page 71
71
11 Supplement
VEGAFLEX 82 • Modbus and Levelmaster protocol
41833-EN-130314
Characteristics and performance data
Measuring cycle time
< 500 ms
Step response time
3)
≤ 3 s
Max. filling/emptying speed
1 m/min
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value
always applies.
The measurement error from the process conditions is in the specified pressure and temperature
range of below 1 %.
Process pressure
-1 … +40 bar/-100 … +4000 kPa (-14.5 … +580 psig),
depending on the process fitting
Vessel pressure relating to the flange
nominal stage
see supplementary instructions manual "Flanges ac-
cording to DIN-EN-ASME-JIS"
Process temperature (thread or flange temperature)
Ʋ FKM (SHS FPM 70C3 GLT)
-40 … +150 °C (-40 … +302 °F)
Ʋ EPDM (A+P 75.5/KW75F)
-40 … +150 °C (-40 … +302 °F)
Ʋ FFKM (Kalrez 6375) - with tempera-
ture adapter
-20 … +200 °C (-4 … +392 °F)
1
2
0°C
(32°F)
-40°C
(-104°F)
65°C
(149°F)
80°C
(176°F)
150°C
(302°F)
130°C
(266°F)
3
4
-40°C
(-104°F)
Fig. 42: Ambient temperature - process temperature, standard version
Cable version with ø 4 mm (0.157 in)
Cable version, PA coated with ø 6 mm (0.236 in)
1 Ambient temperature
2 Process temperature (depending on the seal material)
3 Maximum permissible temperature - standard
4 Limited temperature range - plastic housing and stainless steel housing, electropolished
3)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).