6 Set up with the display and adjustment module

VEGAFLEX 82 • Modbus and Levelmaster protocol

41833-EN-130314

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and

laboratory parameters to the default values of the respective instru-

ment. A created false signal suppression, user programmable lineari-

zation curve as well as the measured value memory will be deleted.
The following table shows the default values of the instrument. De-

pending on the instrument version or application, all menu items may

not be available or some may be differently assigned:

Menu

Menu item

Default value

Setup

Block operation

Released

Measurement

loop name

Sensor

Units

Distance unit: mm
Temperature unit: °C

Probe length

Length of the probe Ex factory

Product type

Bulk solid

Application

Level, vessel

Medium, dielectric

constant

Granules, powder, 1.5 … 3

Max. adjustment

0.000 m(d) - note blocking distances

Min. adjustment

Probe length - take dead band into

account

Linearization

Linear

Damping

0.0 s

Scaling size

Volume in l

Current output,

adjustment

0.00 lin %, 0 l
100.00 lin %, 100 l

Current output

mode

Last measured value

Current output

Min./Max.

Min. current 3.8 mA, max. current

20.5 mA

Display

Language

As set in the device

Displayed value 1 Filling height Level
Displayed value 2 Electronics temperature
Backlight

Switched off