4 mounting – VEGA VEGAFLEX 82 Modbus and Levelmaster protocol User Manual

Page 15

background image

15

4 Mounting

VEGAFLEX 82 • Modbus and Levelmaster protocol

41833-EN-130314

4 Mounting

4.1 General instructions

With instruments with threaded process fitting, suitable tools must be

applied for tightening the hexagon.

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

Use the recommended cables (see chapter "Connecting to power

supply") and tighten the cable gland.
You can give your instrument additional protection against moisture

penetration by leading the connection cable downward in front of the

cable entry. Rain and condensation water can thus drain off. This ap-

plies mainly to:

outdoor mounting

installations in areas where high humidity is expected (e.g. through

cleaning processes)

installations on cooled or heated vessels

In the case of instrument housings with self-sealing NPT threads, it is

not possible to have the cable entries screwed in at the factory. The

openings for the cable glands are therefore covered with red protec-

tive caps as transport protection.
Prior to setup you have to replace these protective caps with ap-

proved cable glands or close the openings with suitable blind plugs.
The suitable cable glands and blind plugs come with the instrument.

Make sure that all parts of the instrument exposed to the process, in

particular the active measuring component, process seal and process

fitting, are suitable for the existing process conditions. These include

above all the process pressure, process temperature as well as the

chemical properties of the medium.
You can find the specifications in chapter "Technical data" and on the

nameplate.

4.2 Instructions for installation

Mount VEGAFLEX 82 in such a way that the distance to vessel instal-

lations or to the vessel wall is at least 300 mm (12 in). In non-metallic

vessels, the distance to the vessel wall should be at least 500 mm

(19.7 in).
During operation, the probe must not touch any installations or the

vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible

nearly down to the lowest point of the bottom. Keep in mind that

measurement all the way down to the tip of the probe may not be pos-

Screwing in

Moisture

Protective caps

Suitability for the process

conditions

Installation position