VEGA VEGAFLEX 82 Modbus and Levelmaster protocol User Manual

Page 16

background image

16

4 Mounting

VEGAFLEX 82 • Modbus and Levelmaster protocol

41833-EN-130314

sible. The exact value of the min. distance (lower dead band) is stated

in chapter "Technical data".

Fig. 6: Vessel with conical bottom

Plastic vessel/Glass vessel

The guided microwave principle requires a metal surface on the pro-

cess fitting. Therefore use in plastic vessels etc. an instrument version

with flange (from DN 50) or place a metal sheet (ø > 200 mm/8 in)

beneath the process fitting when screwing it in.
Make sure that the plate has direct contact with the process fitting.
When installing rod or cable probes without metal vessel wall, e.g.

in plastic vessels, the measured value can be influenced by strong

electromagnetic fields (emitted interference according to EN 61326:

class A).
Use a probe in coax version for applications in liquids.

1

2

Fig. 7: Installation in non-metal vessel
1 Flange

2 Metal sheet

Type of vessel