VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 57

Influence of the ambient temperature to the sensor electronics
7)
Average temperature coefficient of the zero
signal (temperature error)
0.03 %/10 K
Ambient conditions
Ambient, storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process temperature (measured on the process fitting), depending on seal and antenna system
-
FKM (Viton)
-40 … +130 °C (-40 … +266 °F)
-
FFKM (Kalrez 6375)
-20 … +130 °C (-4 … +266 °F)
-
FFKM (Viton) with temperature adapter
-40 … +200 °C (-40 … +392 °F)
-
FFKM (Kalrez 6375) with temperature
adapter
-20 … +200 °C (-4 … +392 °F)
-
FFKM (Kalrez 2035, 6230)
-15 … +130 °C (+5 … +266 °F)
-
FFKM (Kalrez 2035, 6230) with temper-
ature adapter
-15 … +200 °C (+5 … +392 °F)
For the vessel pressure, you also have to note the specifications on the type label. Always the
lowest value is applicable.
Vessel pressure - horn antenna
-
without swivelling holder
-1 … 40 bar/-100 … 4000 kPa (-14.5 … 580 psig)
-
with swivelling holder
-1 … 1 bar/-100 … 100 kPa (-14.5 … 14.5 psig) not
sealing
Vessel pressure - parabolic antenna
-
without swivelling holder
-1 … 6 bar/-100 … 600 kPa (-14.5 … 87 psig)
-
with swivelling holder
-1 … 1 bar/-100 … 100 kPa (-14.5 … 14.5 psig) not
sealing
Vessel pressure relating to the flange nom-
inal stage
see supplementary instructions manual "Flanges
according to DIN-EN-ASME-JIS"
Vibration resistance
8)
-
Horn antenna
mechanical vibrations with 4 g and 5 … 100 Hz
-
Parabolic antenna
mechanical vibrations with 1 g and 5 … 100 Hz
Data on rinsing air connection
Pressure
< 6
bar (87.02 psi)
Air quantity see diagram
7)
Relating to the nominal measuring range, in the temperature range
-40 … +80 °C .
8)
Tested according to the regulations of German Lloyd, GL directive 2.
VEGAPULS
68 • Foundation Fieldbus
57
10 Supplement
29264
-EN
-090305