beautypg.com

VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 42

background image

Note:
Check the distance to the product surface, because if an incorrect (too
large) value is entered, the existing level will be saved as false signal.
The filling level would then no longer be detectable in this area.

The menu item "Extended setting" offers the possibility to optimise
VEGAPULS

68 for applications in which the level changes very

quickly. For this reason, select the function "Quick level change > 1 m/
min.
".

Extended setting

quick level change > 1 m/min.

Note:
Since with the function "Quick level change > 1 m/min." the generation
of an average value of the signal processing is considerably reduced,
false reflections by agitators or vessel installations can cause
measured value fluctuations. A false echo memory is thus recom-
mended.

This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

The following data are read out or written with this function:

l

Measured value presentation

l

Adjustment

l

Medium

l

Standpipe inner diameter

2)

l

Vessel form

l

Damping

l

Linearisation curve

l

Sensor-TAG

l

Displayed value

l

Unit of measurement

l

Language

The following safety-relevant data are not read out or written:

l

PIN

Copy sensor data

Copy sensor data?

2)

With standpipe versions.

Extended setting/Quick
level change

Copy sensor data

42

VEGAPULS

68 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM

29264

-EN

-090305