Instrument does not appear during connection setup

l

Incorrect termination

à Check termination at the beginning and end points of the bus

and terminate, if necessary, according to the specification

l

Instrument not connected to the segment

à Check and correct

In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.

?

E

013

l

no measured value available

à sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or

wrong parameter adjustment

?

E

017

l

Adjustment span too small

à Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E

036

l

no operable sensor software

à Carry out a software update or send the instrument for repair

?

E

041, E042, E043

l

Hardware error, electronics defective

à Exchange instrument or return instrument for repair

?

E

113

l

Communication conflict

à Exchange instrument or return instrument for repair

Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.

8.3 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.

In Ex applications only one instrument and one electronics module with
respective Ex approval may be used.

If there is no electronics module available on site, one can be ordered
from the VEGA agency serving you.

Fault messages via the
indicating/adjustment
module

Reaction after fault rec-
tification

50

VEGAPULS

68 • Foundation Fieldbus

8 Maintenance and fault rectification