beautypg.com

VEGA VEGAMET 602 User Manual

Page 8

background image

8

VEGAMET 601, 602

Electrical separation measures

Reliable separation acc. to VDE 0106,
part 1 between the potentials
- reference voltage

250 V

- isolation resistance

3 kV

Potentials VEGAMET 601
- potential 1

supply voltage

- potential 2

(common minus potenial)

meas. data input (sensor connection),
current output, voltage output

Potential VEGAMET 602
- potential 1

supply voltage

- potential 2

meas. data input (sensor connection)

- potential 3

(common minus potenial)

current output, voltage

- potential 4

fail-safe relays, contacts

CE conformity

VEGAMET signal conditioning instruments meet the protective regulations of EMC
(89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following
standards:
EMC

Emission

EN 50 081 - 1: 1992

Susceptibility

EN 50 082 - 2: 1995

NSR

EN 61 010 - 1: 1993

Ex technical data

Meas. data input (intrinsically safe signal circuit)

Classification

[EEx ia] IIC or [EEx ia] IIB

Max. values
- voltage

U

O

- 20 V

- current

I

O

- 125 mA

- power

P

O

- 624 mW

Characteristics

linear

Effective inner inductance L

i

negligible

Effective inner capacitance C

i

negligible

EEx ia IIC

EEx ia IIB EEx ib IIC EEx ib IIB

Max. permissible outer
inductance L

O

(mH)

0.5

1

1.5

2

2

9

Max. permissible outer
capacitance C

O

(nF)

97

78

68

486

200

1000

The intrinsically safe circuits are reliably separated from the non intrinsically safe circuits up
to a peak voltage of 375 V.
The max. voltage on the non intrinsically safe circuits should not exceed 250 V

eff

in case of

failure.

Product description