VEGA VEGAMET 602 User Manual
Page 8
8
VEGAMET 601, 602
Electrical separation measures
Reliable separation acc. to VDE 0106,
part 1 between the potentials
- reference voltage
250 V
- isolation resistance
3 kV
Potentials VEGAMET 601
- potential 1
supply voltage
- potential 2
(common minus potenial)
meas. data input (sensor connection),
current output, voltage output
Potential VEGAMET 602
- potential 1
supply voltage
- potential 2
meas. data input (sensor connection)
- potential 3
(common minus potenial)
current output, voltage
- potential 4
fail-safe relays, contacts
CE conformity
VEGAMET signal conditioning instruments meet the protective regulations of EMC
(89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following
standards:
EMC
Emission
EN 50 081 - 1: 1992
Susceptibility
EN 50 082 - 2: 1995
NSR
EN 61 010 - 1: 1993
Ex technical data
Meas. data input (intrinsically safe signal circuit)
Classification
[EEx ia] IIC or [EEx ia] IIB
Max. values
- voltage
U
O
- 20 V
- current
I
O
- 125 mA
- power
P
O
- 624 mW
Characteristics
linear
Effective inner inductance L
i
negligible
Effective inner capacitance C
i
negligible
EEx ia IIC
EEx ia IIB EEx ib IIC EEx ib IIB
Max. permissible outer
inductance L
O
(mH)
0.5
1
1.5
2
2
9
Max. permissible outer
capacitance C
O
(nF)
97
78
68
486
200
1000
The intrinsically safe circuits are reliably separated from the non intrinsically safe circuits up
to a peak voltage of 375 V.
The max. voltage on the non intrinsically safe circuits should not exceed 250 V
eff
in case of
failure.
Product description