5 diagnostics, 1 simulation, 2 error codes – VEGA VEGAPULS 54K enamel User Manual
Page 38
38
VEGAPULS 54K enamel
24 101-EN-041227
Diagnostics
5 Diagnostics
5.1 Simulation
To simulate a certain filling level, you can call
up the function “Simulation” in the adjustment
module MINICOM, in the adjustment software
PACT
ware
TM
or in the HART
®
handheld.
You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC,
react according to their settings and will
probably activate alarms or system func-
tions. One hour after the last simulation ad-
justment, the sensor returns automatically to
standard operating mode.
5.2 Error codes
Display
Meaning
Rectifying measure
E013
No valid measured value
Message is displayed during warm-up phase
- Sensor in the warm-up
phase
- Loss of the useful echo
If the message remains, a false echo storage
must be made with the adjustment module
MINICOM in the menu “sensor optimisation” or
better, with the PC and VVO.
If the message still remains, carry out a fresh
adjustment.
E017
Adjustment span too small
Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm.
E036
Sensor software does not
- Sensor must be programmed with new
run
software (service)
- Message appears during a software update.
E040
Hardware failure/Electronics
Check all connection cables.
defective
Contact our service department.