beautypg.com

Electrical connection – VEGA VEGAPULS 54K enamel User Manual

Page 22

background image

22

VEGAPULS 54K enamel

24 101-EN-041227

2

-

+

4 … 20 mA

2

2

2

4

1)

250

2

Measuring system with VEGAPULS 54K in four-wire technology

• Four-wire technology, power supply and output signal via two separate two-wire cables.
• Output signal 4 … 20 mA active.
• Optional external indicating instrument with analogue and digital indication (can be mounted

up to 25 m away from the sensor).

• Adjustment with PC, HART

®

handheld or adjustment module MINICOM (can be plugged into

the sensor or into the indicating instrument VEGADIS 50).

• max. resistance on the signal output (load) 500

(active)

2)

VEGADIS 50

1)

If the resistance of the processing systems
connected to the 4 … 20 mA signal output is less
than 200

Ω, a resistor must be connected to the

connection cable during adjustment to get a loop
resistance of 250

Ω up to 350 Ω.

The digital adjustment signal would otherwise be
severely damped or short-circuited due to
insufficient resistance of the connected process-
ing system. Digital communication with the PC
would not be ensured.

HART

®

handheld

VEGA-
CONNECT 2

Electrical connection

2)

4 … 20 mA active means that the sensor delivers
a level-dependent current of 4 … 20 mA (source).
The sensor reacts electrically in the processing
system (e.g. indication) like a current source.