Electrical connection – VEGA VEGAPULS 54K enamel User Manual
Page 22
22
VEGAPULS 54K enamel
24 101-EN-041227
2
-
+
4 … 20 mA
2
2
2
4
1)
250
Ω
2
Measuring system with VEGAPULS 54K in four-wire technology
• Four-wire technology, power supply and output signal via two separate two-wire cables.
• Output signal 4 … 20 mA active.
• Optional external indicating instrument with analogue and digital indication (can be mounted
up to 25 m away from the sensor).
• Adjustment with PC, HART
®
handheld or adjustment module MINICOM (can be plugged into
the sensor or into the indicating instrument VEGADIS 50).
• max. resistance on the signal output (load) 500
Ω
(active)
2)
VEGADIS 50
1)
If the resistance of the processing systems
connected to the 4 … 20 mA signal output is less
than 200
Ω, a resistor must be connected to the
connection cable during adjustment to get a loop
resistance of 250
Ω up to 350 Ω.
The digital adjustment signal would otherwise be
severely damped or short-circuited due to
insufficient resistance of the connected process-
ing system. Digital communication with the PC
would not be ensured.
HART
®
handheld
VEGA-
CONNECT 2
Electrical connection
2)
4 … 20 mA active means that the sensor delivers
a level-dependent current of 4 … 20 mA (source).
The sensor reacts electrically in the processing
system (e.g. indication) like a current source.