VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire User Manual

Page 51

background image

Input variable

M

easured variable

distance between process fitting and product sur-
face

min. distance from flange

50

mm (1.97 in)

M

easuring range depending on process fitting

-

T

ri-Clamp 2", 3"

up to 10 m (32.81 ft)

-

bolting DN 50, DN 80

up to 10 m (32.81 ft)

-

ange DN 50, ANSI 2"

up to 10 m (32.81 ft)

-

F

lange DN 80 … DN 150, Clamp 4",

ANSI

3" … 6"

up to 20 m (65.62 ft)

Reference conditions to measuring accuracy (according to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

18 … +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

O

ther reference conditions

-

R

eflector

ideal reflector, e.g. metal plate 2 x 2 m

-

F

alse reflections

L

argest false echo 20 dB smaller than the useful

echo

Characteristics and performance data

F

requency

K-

band (26 GHz technology)

M

eas. interval approx.

1

s

B

eam angle -3 dB

5)

-

T

ri-Clamp 2"

18°

-

C

lamp 3", 4"

10°

-

B

olting DN 50

18°

-

B

olting DN 80

10°

-

ange DN 50, ANSI 2"

18°

-

F

lange DN 80 … DN 150, ANSI 3" … 6"

10°

S

tep response or adjustment time

6)

<

1

s (dependent on the parameter settings)

M

ax. level change

A

djustable up to 1 m/min. (dependent on the

parameter settings)

M

ax. emitted HF power of the antenna system

-

P

ulse peak power

<

2

mW

-

P

ulse duration

<

2

ns

5)

C

orresponds to the range with 50 % of the emitted power

6)

T

ime to output the correct level (with max. 10 % deviation) after a sudden

level change.

VEGAPULS

63 • 4 … 20

mA/HART - two-wire

51

10 A

nnex