VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire User Manual

Page 34

background image

M

edium

L

iquid

Information:
W

ith VEGAPULS 63 with electronics version "Increased safety",

"

Solid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the medium selection should
be set to "Liquid" during setup.

A

ccording to the conductivity and the dielectric figure of liquids, the

reflection properties can differ considerably. Therefore additional
options such as "Solvent", "Chem. mixture" and "Water based" are
offered below the menu item Liquid.

W

ith solids, you can also choose between "Powder/Dust", "Granular/

Pellets" or "Ballast/Pebbels".

T

hrough this additional selection, the sensor is adapted perfectly to the

product and measurement reliability, particularly in products with poor
reflective properties, is considerably increased.

E

nter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A

part from the medium, the vessel shape can also influence the

measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or bulk
solid is selected. With "Liquids" these are "Storage tank", "Stilling
tube
", "Open vessel" or "Stirred vessel", with "Solid", "Silo" or
"

Bunker".

V

essel form

Storage tank

Information:
W

ith VEGAPULS 63 with electronics version "Increased safety",

"

Solid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the vessel form should be set
to "Storage tank" during setup.

E

nter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A

linearisation is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. in a horizontal cylindrical
or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed for

Vessel form

Linearisation curve

34

VEGAPULS

63 • 4 … 20

mA/HART - two-wire

6 S

et up with the indicating and adjustment module PLICSCOM

28436

-EN

-120530