3 exchanging the electronics module – VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART - two-wire User Manual
Page 46
Error
Cause
Rectification
O
perating voltage
too low or load
resistance too
high
C
heck, adapt if necessary
C
urrent signal
greater than 22 mA
or less than
3.6
mA
E
lectronics mo-
dule in the sensor
defective
E
xchange the instrument or send it in
for repair
I
n Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or
wrong parameter adjustment
?
E
017
l
A
djustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E
036
l
no operable sensor software
à Carry out a software update or send instrument for repair
?
E
041, E042, E043
l
H
ardware error, electronics defective
à Exchange the instrument or send it in for repair
D
epending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.
8
.3 Exchanging the electronics module
I
f the electronics module is defective, it can be replaced by the user.
I
n Ex applications only one instrument and one electronics module with
respective Ex approval may be used.
I
f there is no electronics module available on site, one can be ordered
from the VEGA agency serving you.
T
he new electronics module must be loaded with the settings of the
sensor. These are the options:
Error messages via the
indicating and adjust-
ment module
Reaction after fault rec-
tification
Sensor serial number
46
VEGAPULS
63 • 4 … 20
mA/HART - two-wire
8 M
aintenance and fault rectification
28436
-EN
-120530