VEGAPULS 43 – 4 … 20 mA
26626-EN-041227
Technical data
Parameter and measuring range
1)
Parameter
distance between product surface and
process fitting (e.g. lower flange side
of the sensor)
Measuring range
- DN 50, ANSI 2“
0 … 10 m
- DN 80, ANSI 3“
0 … 20 m
- DN 100, ANSI 4“
0 … 20 m
- DN 150, ANSI 6“
0 … 20 m
- TRI-Clamp 2“, 3“
0 … 10 m
- socket DN 50, DN 80
0 … 10 m
Output signal
Signal output
4 … 20 mA current signal in two-wire or
four-wire technology; the HART
®
signal is
modulated to the 4 … 20 mA signal
Fault signal
current output unchanged, 20.5 mA, 22 mA
(adjustable)
Resistance/Load of the signal cable
- 4 … 20 mA two-wire
non-Ex:
max 975
Ω
Ex d ia:
max. 720
Ω
Ex ia:
max. 670
Ω
- 4 … 20 mA four-wire
500
Ω
Integration time
- analogue 4 … 20 mA
0 … 999 seconds
Two-wire technology 4 … 20 mA:
The analogue 4 … 20 mA output signal (measuring signal) is transmitted together with the
power supply via one two-wire cable.
Four-wire technology 4 … 20 mA:
Separate power supply. The analogue 4 … 20 mA output signal (measuring signal) is
transmitted in a cable separate from power supply.
Measured value display (optional)
Liquid crystal indication
- in the sensor
scalable output of measured values as graph
and number
- in the external indicating instrument
powered by the sensor
scalable output of measured values as graph
and number. The display unit can be mounted
up to 25 m away from the sensor
Adjustment
- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- HART
®
handheld
1)
Min. distance of the antenna to the medium 5 cm