VEGA VEGABAR 61 Foundation Fieldbus User Manual
Page 65
l
sensor_range
-
"S
ensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'
-
includes sensor unit: bar, PSI …; only unit part of DS-68 is writable
l
simulate_primary_value
l
simulate_secondary_value_1
l
simulate_secondary_value_2
l
device status
-
"
0: ""OK"" 13: ""non-specific error"" 17: ""Cal span too small"" 34: ""EEPROM memory fault"" 36:
""ROM
memory fault"" 37: ""RAM memory fault"" 40: ""non-specific hardware fault"" 41: ""Sensor
element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI error"" 113:
""C
ommunication hardware fault"""
l
linearization type
-
Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container
-
"
0: ""Linear"" 1: ""User def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""
l
curve_points_1_10
-
X and Y values for the user defined linearization curve
l
curve_points_11_20
-
X and Y values for the user defined linearization curve
l
curve_points_21_30
-
X and Y values for the user defined linearization curve
l
curve_points_31_33
-
X and Y values for the user defined linearization curve
l
curve status
-
Result of table plausibility check
-
"
0: ""Uninitialized"" 1: ""Good"" 2: ""Not monotonous increasing"" 3: ""Not monotonous
decreasing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6:
""G
radient of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9: ""Sorting
and checking table"""
l
SUB_DEVICE_NUMBER
l
SENSOR_ELEMENT_TYPE
-
0: "non-specific"
l
display_source_selector
-
Selects the type of value that is displayed on the indication-/adjustement-module
-
"
0: ""Physical value"" 1: ""Percent value"" 2: ""Lin percent value"" 6: ""Out(AI1)"" 7: ""Level"" 8:
""O
ut(AI2)"" 9: ""Out(AI3)"""
l
max_peak_sensor_value
-
Holds the maximum sensor value. Write access resets to current value. Unit derives from
'S
ensor_range.unit'
-
Write access resets to current value
l
min_peak_sensor_value
-
Holds the minimum sensor value. Write access resets to current value. Unit derives from
'S
ensor_range.unit'
-
Write access resets to current value
l
CAL_POINT_HI
VEGABAR
61 • Foundation Fieldbus
65
10 Supplement
28258
-
EN
-081209