VEGA VEGABAR 61 Foundation Fieldbus User Manual
Page 20
2
Remove the housing socket from the mounting plate
3
2
1
Fig. 7: Components of the external housing for plics
®
devices
1
Screws
2
Wall mounting plate
3
Cable gland
3
Loop the connection cable through the cable entry on the housing
base
2)
Information:
The cable gland can be mounted in three positions each displaced by
90°. Simply exchange the cable gland against the blind plug in the
suitable thread opening.
4
Connect the wire ends as described under "Single/Double
chamber housing" according to the numbering
5
Connect the screen to the internal ground terminal, connect the
outer ground terminal above on the housing to potential equal-
isation
6
Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
7
Attach the mounting plate again and tighten the screws
The electrical connection of the sensor to the external housing is
hence ready.
2)
The connection cable is already preconfectioned. If necessary, shorten it to
the requested length, cut the breather capillaries clean. Remove approx.
5 cm of the cable mantle, strip approx. 1 cm insulation from the ends of the
individual wires. After shortening the cable, fasten the type plate with sup-
port back onto the cable.
20
VEGABAR
61 • Foundation Fieldbus
5 Connecting to power supply
28258
-EN
-081209