This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
l
Measured value presentation
l
Adjustment
l
Damping
l
Linearisation curve
l
Sensor-TAG
l
Displayed value
l
Unit of measurement
l
Language
The following safety-relevant data are not read out or written:
l
PIN
l
Application
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
8)
Menu section
Function
Reset value
Basic settings
Unit of measurement
bar
Temperature unit
°C
Zero/Min. adjustment
Measuring range begin
Span/Max. adjustment
Measuring range end
Density
1 kg/l
Density unit
kg/l
Damping
0 s
Linearisation
linear
Sensor-TAG
Sensor
Display
Displayed value
AI-Out
The values of the following menu items are not reset with "Reset:
Menu section
Function
Reset value
Basic settings
Position correction
no reset
Display
Lighting
no reset
Service
Language
no reset
8)
Sensor-specific basic adjustment.
Copy sensor data
Reset
VEGABAR
61 • Foundation Fieldbus
41
6 Set up with the indicating and adjustment module PLICSCOM