VEGA VEGABAR 61 Foundation Fieldbus User Manual
Page 39
2
Confirm the menu "Basic adjustment" with [OK], the menu item
"U
nit" will be displayed.
Unit
Unit of measurement
bar
▼
Temperature unit
°C
▼
3
Activate the selection with [OK] and select "Units of measure-
ment with [->].
4
Activate the selection with [OK] and select the requested unit with
[->]
(in the example mbar).
5
Confirm with [OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to mbar.
Proceed as follows to select the temperature unit:
7)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->]
(e.g. °F).
à Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1
Activate in the menu item "Position correction" the selection with
[OK]
.
Position correction
Offset
P
=
+
0000 mbar
53 mbar
2
Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
▶
Accept
Edit
3
Confirm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1
Edit the mbar value in the menu item "zero" with [OK].
7)
Selection options: °C, °F.
Carry out position cor-
rection
Carrying out zero ad-
justment
VEGABAR
61 • Foundation Fieldbus
39
6 Set up with the indicating and adjustment module PLICSCOM
28258
-
EN
-081209