VEGA VEGABAR 61 Foundation Fieldbus User Manual

Page 39

background image

2

Confirm the menu "Basic adjustment" with [OK], the menu item
"U

nit" will be displayed.

Unit
Unit of measurement

bar

Temperature unit

°C

3

Activate the selection with [OK] and select "Units of measure-
ment
with [->].

4

Activate the selection with [OK] and select the requested unit with
[->]

(in the example mbar).

5

Confirm with [OK] and move to position correction with [->].

The adjustment unit is hence switched over from bar to mbar.

Proceed as follows to select the temperature unit:

7)

à Activate the selection with [OK] and select "Temperature unit

with [->].

à Activate the selection with [OK] and select the requested unit with

[->]

(e.g. °F).

à Confirm with [OK].
The temperature unit is hence switched over from °C to °F.

Proceed as follows:

1

Activate in the menu item "Position correction" the selection with
[OK]

.

Position correction
Offset

P

=

+

0000 mbar

53 mbar

2

Select with [->], e.g. to accept actual measured value.

Position correction
Accept current measured

value?

Accept

Edit

3

Confirm with [OK] and move to min.(zero) adjustment with [->].

Proceed as follows:

1

Edit the mbar value in the menu item "zero" with [OK].

7)

Selection options: °C, °F.

Carry out position cor-
rection

Carrying out zero ad-
justment

VEGABAR

61 • Foundation Fieldbus

39