VEGAFLEX 51P and 52P

Setup

Start

If you click to "Start", the echo curve will be
updated continuously. With "Stop" you can
terminate the update.

Empty vessel profile

With the functions in this window you can
gate out false echoes. The blue empty vessel
profile curve in the echo curve window shows
the actual empty vessel profile.

Determine the level by sounding. If the sen-
sor has identified a false echo as most prob-
able echo instead of the actual filling level,
you can gate the echo out.

Choose the function "Create new". Enter the
measured distance to the medium. All false
echoes in the range up to the adjusted dis-
tance are automatically gated out.

With "Update" you can extend the empty
vessel profile if new false echoes occur as
the level falls. If you want to delete the exist-
ing empty vessel profile, click to "Cancel".