9 Supplement
VEGAMET 381 • 4 … 20 mA signal conditioning instrument
27567-01-131025
Switching current
min. 10 µA DC, max. 3 A AC, 1 A DC
Breaking capacity
min. 50 mW, max. 500 VA, max. 54 W DC
2)
Min. switching hysteresis
0.5 %
Current output
Quantity
1 x output
Range
0/4 … 20 mA
Resolution
0.1 %/20 µA
Max. load
500 Ω
Fault message
22 mA
Accuracy
±25 µA (0.125 % of 20 mA)
Temperature error (relating to 20 mA)
0.01 %/K
Indications
Measured value indication
Ʋ LC display (45 x 45 mm)
digital and quasianalogue indication
Ʋ Max. indicating range
-9999 … 9999
LED displays
Ʋ Status operating voltage
1 x LED green
Ʋ Status fault signal
1 x LED red
Ʋ Status operating relay 1/2
2 x LED yellow
Operation
Adjustment elements
2 x key, 1 x function selection switch
Ambient conditions
Ambient temperature
-20 … +60 °C (-4 … +140 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Electrical protective measures
Protection rating
Ʋ Wall, rail mounting
IP 20
Ʋ Front panel mounting
IP 40
Overvoltage category
II
Protection class
II
Electrical separating measures
Reliable separation according to VDE 0106 part 1 between power supply, sensor input and digital
component
Ʋ Reference voltage
250 V
Ʋ Voltage resistance of the isolation
3.75 kV
2)
If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be
permanently damaged. The contact is then no longer suitable for switching low-level signal circuits.