6 Setup with the integrated display and adjustment unit

VEGAMET 381 • 4 … 20 mA signal conditioning instrument

27567-01-131025

If potential equalisation currents are expected,

the screen connection on the side of VEGAMET

381 must be made via a ceramic capacitor

(e. g. 1 nF, 1500 V). The low frequency potential

equalisation currents are thus suppressed, but

the protective effect against high frequency

interference signals remains.
Select connection cable for Ex applications

Take note of the corresponding instal-

lation regulations for Ex applications. In

particular, make sure that no potential

equalisation currents flow over the cable

screen. In case of grounding on both

sides this can be achieved by the use

of a capacitor or a separate potential

equalisation.

5.2 Input mode active/passive

With the function switch you can changeover

between active and passive operation of the

measuring data input.

In active mode, VEGAMET 381 provides

the power for the connected sensors. Power

supply and measurement data are transmit-

ted over the same two-wire cable. This mode

is provided for connection of measuring

transducers without separate operating

voltage (sensors in two-wire version).

In passive mode the sensors are not powe-

red, only the measured value is transmitted.

This input is for connection of transmitters

with their own separate operating voltage

(sensors in four-wire version). The VEGA-

MET 381 can be also looped into the exis-

ting circuit like a normal ammeter.

5.3 Connection procedure

Proceed as follows:
1. Mount VEGAMET 381
2. Connect sensor cable to terminal 1 and 2,

and where applicable, connect the screen

3. Connect power supply (switched off) to

terminal 5 and 6

4. If necessary, connect fail safe and operating

relay as well as current output

The electrical connection is hence finished.

5.4 Wiring plan

Overview

+ -

1 2

+ -

3 4

18 17 16 15 1413 1211 10 9 8 7 6 5

N- L1+

on

1
2

1

2

%

1

2

3

7

4

5

6

Abb. 13: Wiring plan with two-wire sensor
1 Measurement data input, optionally available with

sensor power supply

2 Current output

3 Fail safe relay

4 Relay 2

5 Relay 1

6 Voltage supply

Tipp:

For parameter adjustment of connec-

ted HART sensors, the sockets are

integrated in the terminals of the meas.

data input. A VEGACONNECT can be

directly plugged in without the need of

an additional HART resistor.

6 Setup with the integrated

display and adjustment

unit

6.1 Adjustment system

The integrated display and adjustment unit is

for measured value display, adjustment and

diagnosis ofVEGAMET 381. Indication and

adjustment is carried out in the front via a clear

LC-display and a function switch as well as two

keys.
To open the cover, insert a screwdriver in the

two slots on the top and turn it slightly.