beautypg.com

4 mounting – VEGA VEGAMET 381 User Manual

Page 22

background image

22

4 Mounting

VEGAMET 381 • 4 … 20 mA signal conditioning instrument

27567-01-131025

Functional principle

The VEGAMET 381 signal conditioning instru-

ment can power connected sensors and pro-

cess their measurement signals. The requested

measured variable is shown on the display and

also outputted to the integrated current output

for further processing. The measurement signal

can thus be transferred to a remote indication or

a superordinate control system. Two level relays

for control of pumps or other devices are also

integrated.
Voltage supply

Wide-range power supply unit with

20 … 253 V AC/DC for world-wide use.
Detailed information about the power supply

can be found in chapter "Technical data".

3.3 Operation

The adjustment of VEGAMET 381 is carried out

via the integrated keys and a 16-step function

switch.

3.4 Packaging, transport and

storage

Packaging

Your instrument was protected by packaging

during transport. Its capacity to handle normal

loads during transport is assured by a test

based on ISO 4180.
The packaging of standard instruments consists

of environment-friendly, recyclable cardboard.

For special versions, PE foam or PE foil is also

used. Dispose of the packaging material via

specialised recycling companies.
Transport

Transport must be carried out in due conside-

ration of the notes on the transport packaging.

Nonobservance of these instructions can cause

damage to the device.
Transport inspection

The delivery must be checked for completeness

and possible transit damage immediately at re-

ceipt. Ascertained transit damage or concealed

defects must be appropriately dealt with.
Storage

Up to the time of installation, the packages

must be left closed and stored according to the

orientation and storage markings on the outside.
Unless otherwise indicated, the packages must

be stored only under the following conditions:

Not in the open

Dry and dust free

Not exposed to corrosive media

Protected against solar radiation

Avoiding mechanical shock and vibration

Storage and transport temperature

Storage and transport temperature see

chapter "Supplement - Technical data -

Ambient conditions"

Relative humidity 20 … 85 %

4 Mounting

4.1 General instructions

Installation possibilities

The instrument is designed for recessed ins-

tallation in a front panel, housing front plate or

a switching cabinet door. The required cut-out

is 92 x 92 mm (3.63 x 3.63 in) according to

EN 60529. When installed correctly, protection

rating IP 40 is guaranteed. As an alternative,

the instrument can be mounted into a switching

cabinet or housing by means of three screws

(fixed with screws on rear of housing). A moun-

ting adapter for carrier rail mounting is optionally

available in the scope of delivery (top hat rail

35 x 7.5 according to DIN EN 50022/60715).

Information:

If the instrument is mounted via the

screws or carrier rail, it must always be

inside a switching cabinet or protective

case.

4.2 Mounting instructions

Front panel mounting

1. Make sure that the cutout required for

installation has a size of 92 x 92 mm

(3.63 x 3.63 in). The required installation

depth is min. 90 mm (3.54 in).

2. Remove the pluggable terminal strips from

the top and bottom.

3. Screw the threaded pin [3] into the rear of

the instrument and tighten with a screwdri-

ver.