6 Setup with the integrated display and adjustment unit

VEGAMET 381 • 4 … 20 mA signal conditioning instrument

27567-01-131025

2

1

3

off (on)

on (off)

o n

o n

o f f

o f f

t

L E D

Abb. 15: Relay modes
1 Filling height

2 Mode overfill protection

3 Mode dry run protection

Scaling

Scaling means converting the measured value

into a certain parameter and unit. The indication

can then show the volume in litres e.g., instead

of the percentage value. Indication values from

-9999 to +9999 are possible.
1. First of all, determine the max. indicating

range and the number of decimal places

after the decimal point -- max. four decimal

places can be displayed. Select position [

5 ] of the function switch, place the decimal

point in the required position and save your

settings.

2. Now select position [6] or [7] on the function

switch, enter the requested values for

100 % or 0 % and save your settings.

Damping

To suppress fluctuations in the measured value

display, e.g. caused by an agitated product sur-

face, an integration time can be set. This time

can be between 0 and 250 seconds. Remember

that the reaction time of the entire measurement

will then be longer and the sensor will react

to measured value changes with a delay. In

general, a period of a few seconds is sufficient

to smooth the measured value display.

Now select position [9] on the function

switch, enter the requested value and save

your settings

Current output 0/4 … 20 mA

The characteristics of the current output can be

switched over from 4 … 20 mA to 0 … 20 mA.

Now select position [8] on the function

switch, adjust the requested characteristics

curve and save your settings

Simulation

To check if the settings ofVEGAMET 381 are

correct, the simulation mode can be used. Any

individual measured value can be simulated

and e.g. the correct behaviour of the relays and

the connected instruments can be checked.
Switching over between the functions "OPERA-

TE" and "Simulation" is done by pushing the [+/-

] keys for at least 3 seconds. In the simulation

mode, the set value flashes on the display. The

simulation can be switched off by pushing both

keys again for approx. 3 seconds. If no key is

pushed, the display switches automatically over

to "OPERATE" after approx. 60 minutes and the

simulation is terminated.

To start simulation, push the [ +/-] keys si-

multaneously until the displayed value starts

flashing (approx. 3 seconds). By pushing

either of the [ +/-] keys, you can set the

requested simulation value and carry out

your check.

Reset

With a reset, all values set by the user will be

lost and are reset to factory settings.

Interrupt the power supply of VEGAMET

381. Push the [+/-] keys simultaneously and

hold them while you switch on the power

supply. The display shows "RES" and the

default settings will be restored. These are

the following:

Relay switch on points: 10 %

Relay switch off points: 100 %

Decimal point: 888.8

Display min.: 0

Display max.: 100.0

Integration time: 0 s

Offset correction: 0

Current output: 4 … 20 mA

Min. adjustment: 0 % or 4 mA

Max. adjustment: 100 % or 20 mA