3 continuous level measurement – VEGA Capacitive electrodes EL … User Manual
Page 37
Capacitive electrodes EL …
37
Set-up
4.3 Continuous level measurement
When you have already stated the measured product with the order, the oscillator of the electrode
is already preadjusted. In this case the measured product is mentioned on the order confirmation.
• Choose with the changeover switch on the oscillator of the electrode the step according to the
following table.
Note the column corresponding to your medium and choose by means of the length of your
electrode the suitable range.
The stated lengths partly do not correspond to the actually available electrodes. If you are not
sure always set the changeover switch to the next higher step.
Medium
Non-conductive
Non-conductive
Conductive
1)
EL-Type
and DK = 2
and DK = 10
or DK > 50
EL 11
0 - 5,5 m
Range 1
0 - 0,8 m
Range 1
––
––
0,8 - 4,5 m
Range 2
––
EL 11 with concentric tube
0 - 1,5 m
Range 1
0 - 0,15 m
Range 1
––
––
0,15 - 0,9 m Range 2
––
EL 18
0 - 6 m
Range 1
0 - 1 m
Range 1
––
––
1 - 5,5 m
Range 2
––
EL 21 (2 mm-isolation)
0 - 5 m
Range 1
0 - 1,1 m
Range 1
0 - 0,25 m
Range 1
––
1,1 - 6 m
Range 2
0,25 - 1,4 m
Range 2
EL 21 (2 mm-isolation)
0 - 2 m
Range 1
0 - 0,5 m
Range 1
0 - 0,3 m
Range 1
with concentric tube
––
0,5 - 2,5 m
Range 2
0,3 - 1,7 m
Range 2
EL 21 (3,2 mm-isolation)
0 - 6 m
Range 1
0 - 1,5 m
Range 1
0 - 0,6 m
Range 1
––
1,5 - 6 m
Range 2
0,6 - 3 m
Range 2
EL 21 (3,2 mm-isolation
0 - 3,5 m
Range 1
0 - 1 m
Range 1
0 - 0, m
Range 1
with concentric tube
––
1 - 5,5 m
Range 2
0,7 - 4 m
Range 2
EL 24
0 - 6 m
Range 1
0 - 1 m
Range 1
0 - 0,15 m
Range 1
––
1 - 5,5 m
Range 2
0,15 - 0,8 m
Range 2
EL 24 with concentric tube
0 - 2 m
Range 1
0 - 0,4 m
Range 1
0 - 0,15 m
Range 1
––
0,4 - 2 m
Range 2
0,15 - 0,9 m
Range 2
EL 28
0 - 6 m
Range 1
0 - 1,5 m
Range 1
0 - 0,5 m
Range 1
––
1,5 - 6 m
Range 2
0,5 - 2,8 m
Range 2
EL 29
0 - 6 m
Range 1
0 - 1 m
Range 1
0 - 0,3 m
Range 1
––
1 - 5 m
Range 2
0,3 - 1,8 m
Range 2
EL 31
0 - 6 m
Range 1
0 - 1 m
Range 1
––
6 - 30 m
Range 2
1 - 5 m
Range 2
––
EL 33
0 - 6 m
Range 1
0 - 1 m
Range 1
––
6 - 30 m
Range 2
1 - 5 m
Range 2
––
EL 34
0 - 6 m
Range 1
0 - 1 m
Range 1
––
6 - 30 m
Range 2
1 - 5,5 m
Range 2
––
EL 42
0 - 9 m
Range 1
0 - 2 m
Range 1
0 - 0,8 m
Range 1
9 - 30 m
Range 2
2 - 10 m
Range 2
0,8 - 4,5 m
Range 2
EL 52
0 - 6 m
Range 1
0 - 1,6 m
Range 1
0 - 0,7 m
Range 1
6 - 30 m
Range 2
1,6 - 8 m
Range 2
0,7 - 4 m
Range 2
EL 53
0 - 6,5 m
Range 1
0 - 1,5 m
Range 1
0 - 0,5 m
Range 1
6,5 - 30 m
Range 2
1,5 - 8 m
Range 2
0,5 - 2,5 m
Range 2
EL 60
0 - 5,5 m
Range 1
0 - 0,8 m
Range 1
––
––
0,8 - 4,5 m
Range 2
––
EL 61
0 - 6 m
Range 1
0 - 1 m
Range 1
––
6 - 30 m
Range 2
1 - 5 m
Range 2
––
1)
Oscillator E17 up from a conductivity > 10
µ
S, oscillator E18 up from a conductivity > 100
µ
S.