beautypg.com

Separate housing – VEGA Capacitive electrodes EL … User Manual

Page 34

background image

34

Capacitive electrodes EL …

Electrical connection

Separate housing

When there are ambient temperatures of more
than 80

°

C on the housing, a temperature

adapter must be used or the electronics must
be separated from the electrode and located at
a cool place. Hence the electronics can be
mounted in a separate housing at a distance of
up to 8 m from the electrode. Electrode and
housing are dispatched completely mounted.

Carry out the adjustment according to the
following figures. Only use VEGA-triax cable.

Choose the cable connection as short as
possible.

Capacitive rod and cable electrodes EL

Electrode EL 26 (EL 35) for adhesive
products

black

red

black

red

blue
(screen)