VEGA Capacitive electrodes EL … User Manual
Page 10
10
Capacitive electrodes EL …
Oscillators in two-wire technology for capacitive electrodes EL
Type
Application
Meas. range Meas. frequency
Signal
conditioning
instrument
E14
Level detection in general
I: 0 … 25 pF
400 kHz
VEGATOR
II: 0 … 100 pF
VEGALOG
III: 0 … 400 pF
E15
Level detection in general
I: 0 … 25 pF
400 kHz
VEGATOR
with potential separation
II: 0 … 100 pF
VEGALOG
III: 0 … 400 pF
E15 Ex
like E15, however for the use in
I: 0 … 25 pF
400 kHz
VEGATOR Ex
hazardous areas according to
II: 0 … 100 pF
VEGALOG
1)
CENELEC, PTB zone 0 as well as
III: 0 … 400 pF
zone 0 and StEx zone 10 and as
part of an overfill protection acc. to
WHG (VbF)
E17
Continuous level measurement
I: 0 … 120 pF
40 kHz
VEGAMET
in general or level detection
II: 0 … 600 pF
VEGALOG
with potential separation
III: 0 … 3000 pF
(VEGATOR)
E17 Ex
like E17, however for the use in
I: 0 … 120 pF
40 kHz
VEGAMET Ex
hazardous areas according to
II: 0 … 600 pF
VEGALOG
1)
CENELEC, PTB zone 0 as well as
III: 0 … 3000 pF
(VEGATOR Ex)
zone 0 and StEx Zone 10 and as
part of an overfill protection acc. to
WHG (VbF)
E18
2)
Continuous level measurement
I: 0 … 120 pF
470 kHz
VEGAMET
or level detection with potential
II: 0 … 600 pF
VEGALOG
separation according to the principle of
III: 0 … 3000 pF
(VEGATOR)
phase selective admittance proces-
sing especially for adhesive
products and for use in solids with
varying humidity
E18 Ex
2)
like E18, however for the use in
I: 0 … 120 pF
470 kHz
VEGAMET Ex
hazardous areas according to
II: 0 … 600 pF
VEGALOG
1)
CENELEC, PTB zone 0 as well as
III: 0 … 3000 pF
(VEGATOR Ex)
zone 0 and StEx zone 10 and as
part of an over fill protection acc. to
WHG (VbF)
1)
with safety barrier
2)
see following page
Product description